Metal Stud Limiting Heights & Spans Tables

Metal Stud Limiting Heights & Span Tables: What Every Contractor Needs to Know

You’ve probably heard someone on a job site ask “what’s the limiting height on that wall?” — or pulled up a span table to check a floor joist before ordering. These tables show up across every phase of a cold-formed steel project, from estimating to field framing. But they’re not all the same table. Depending on what you’re building, you may be looking at one of four different systems: interior wall heights, exterior curtain wall heights, floor joist spans, or ceiling framing spans — each with its own inputs and rules.

This guide breaks down all four in plain terms: what each table is for, what goes into it, how to read the numbers, and what to watch out for. All data is drawn directly from ClarkDietrich’s published load tables (AISI S100-16 w/S2-20, IBC 2024).

Table of Contents

What Does “Limiting Height” Actually Mean?

A limiting height — or allowable span, for horizontal members — is the maximum distance a cold-formed steel stud or joist can span before it bends too much. Not before it breaks. Before it deflects more than what the wall finish or floor system can handle without cracking, buckling, or failing.

Think of it this way: a 20-gauge stud might be plenty strong enough to hold up a wall, but if that wall is too tall for that gauge at that spacing, the stud will flex enough under wind or occupancy pressure to crack the drywall. The limiting height is the cutoff where that flex becomes a problem.

This is a serviceability issue, not a structural failure issue. The distinction matters because a stud can be within its load capacity and still exceed its limiting height for its finish type — and that shows up as cracked tape, buckled gypsum, or failed tile.

Deflection Limits — The Number Behind the Slash

Every limiting height and span table is built around a deflection limit — written as L/something, where L is the clear height or span in inches. The number after the slash tells you how much movement is allowed: the bigger the number, the less movement is permitted.

Here’s a concrete example. If your wall is 20 feet tall, that’s 240 inches. At L/240, you’re allowed 1 inch of movement. At L/600, you’re allowed less than half an inch. See Table 1 for the full breakdown.

Deflection Limit Max movement on a 20' (240") span Where it typically shows up
L/1202 inchesLight-duty interior partitions
L/2401 inchStandard drywall walls; exterior EIFS/siding; floor total load
L/360¾ inchTile or plaster interiors; exterior stucco; floor live load
L/480½ inchStiffer floor spec — some commercial floors require this
L/600⅖ inchExterior brick veneer
L/720⅓ inchBrick veneer, more restrictive specs

Table 1: How deflection limits translate to actual movement on a 20-foot span. L = clear height or span in inches.

The tighter the limit, the stiffer the assembly needs to be — which means heavier gauge, closer spacing, deeper stud, or some combination. This is where a lot of the cost decisions in CFS framing happen.

Where do you find the required deflection limit? On the project’s architectural drawings or specs. The finish schedule will tell you what’s going on the wall, and that determines which limit applies. When in doubt, ask the engineer of record.

The Four Table Systems at a Glance

Before pulling numbers from any limiting height table, you need to know which system you’re in. The four systems have different load inputs, different deflection limits, and different member types. Pulling a number from the wrong system is one of the most common errors in CFS framing. See Table 2 for a side-by-side comparison.

System What it covers Load input Deflection limits used
Interior Wall Heights Non-load-bearing partition walls inside a building Lateral pressure: 5, 7.5, or 10 psf L/120, L/240, L/360
Exterior Curtain Wall Heights Structural stud backup for exterior cladding — brick, EIFS, stucco, panels Wind pressure (ASD, psf) L/240, L/360, L/600, L/720
Floor Joist Spans CFS C-joists carrying floor loads Total load + live load (psf) Total load: L/240; Live load: L/360 or L/480
Ceiling Framing Spans ProSTUD, furring channel, or U-channel supporting a ceiling assembly Dead load (weight of ceiling): 4, 6, or 13 psf L/240 or L/360

Table 2: The four CFS load table systems. Source: ClarkDietrich Load Tables (IBC 2024 / AISI S100-16 w/S2-20).

Interior Wall Heights

This is the table most framers reach for first on a typical commercial job. Interior wall height tables tell you the maximum height for a non-load-bearing partition wall — a wall that divides space but doesn’t carry floors or roof structure above it.

Even though these walls don’t carry vertical loads, they still need to handle horizontal pressure — people leaning against them, HVAC pressure, and a minimum occupancy load the IBC requires for all interior partitions (5 psf). That lateral pressure is what the table is sizing the stud against.

What you need to look up a number:

  • Stud size and gauge (see the “How to Read a Stud Designation” section below)
  • Stud spacing — 12″, 16″, or 24″ on-center
  • Lateral load — 5 psf for most interior walls; 7.5 or 10 psf for shaft walls, stairwells, or wherever your spec calls it out
  • Deflection limit — L/240 for standard drywall; L/360 if the wall gets tile, plaster, or cement board (see Table 3)
Finish type Deflection limit to use
Standard gypsum board (both sides)L/240 — IBC default per AISI S240
Ceramic tile, stone veneer, plaster, cement boardL/360 — brittle finishes need a stiffer assembly
Utilitarian / light-duty partitionsL/120 — only where spec explicitly allows; rarely used in commercial work

Table 3: Which deflection limit to use based on interior wall finish type.

Always check the finish schedule. The deflection limit isn’t set by the stud — it’s set by what’s going on the wall. A tile bathroom wall and a painted drywall corridor wall might use the same stud, but the tile wall needs L/360, which means a shorter allowable height or a heavier stud. Miss that and you’ll be back to fix cracked grout.

The values in these tables assume the stud has continuous lateral support along its full height — meaning sheathing or drywall is applied to both sides all the way up. If the wall won’t be fully sheathed during construction, bridging needs to be in place first. The tables also assume no vertical load on the stud. If any floor or roof load bears on the wall, you’re outside the scope of these tables and need an engineer’s input.

Where a height value is followed by an “e,” web stiffeners are required at the bearing points. Without them, that published height doesn’t apply.

Tables 4 and 5 show example reference data for 2-1/2″ and 3-1/2″ structural studs at 5 psf lateral load.

Stud Spacing L/120 L/240 L/360
250S137-3312" oc17' 6"13' 10"12' 1"
250S137-3316" oc15' 10"12' 7"11' 0"
250S137-3324" oc13' 10"11' 0"9' 7"
250S137-5412" oc20' 3"16' 1"14' 1"
250S137-5416" oc18' 5"14' 8"12' 9"
250S137-5424" oc16' 1"12' 9"11' 2"
250S162-6812" oc22' 9"18' 1"15' 9"
250S162-6816" oc20' 8"16' 5"14' 4"
250S162-6824" oc18' 1"14' 4"12' 6"
250S162-9712" oc25' 0"19' 10"17' 4"
250S162-9716" oc22' 9"18' 0"15' 9"
250S162-9724" oc19' 10"15' 9"13' 9"

Table 4: 2-1/2" interior wall heights, 5 psf lateral load. "e" after a value indicates web stiffeners required at bearing. Source: ClarkDietrich Structural Interior Wall Heights (IBC 2024 / AISI S100-16 w/S2-20).

Stud Spacing L/120 L/240 L/360
350S137-3312" oc22' 7"17' 11"15' 8"
350S137-3316" oc20' 7"16' 4"14' 3"
350S137-3324" oc17' 2"14' 3"12' 5"
350S137-4312" oc24' 7"19' 6"17' 1"
350S137-4316" oc22' 4"17' 9"15' 6"
350S137-4324" oc19' 6"15' 6"13' 6"
350S137-6812" oc28' 2"22' 4"19' 6"
350S137-6816" oc25' 7"20' 3"17' 9"
350S137-6824" oc22' 4"17' 9"15' 6"
350S137-9712" oc30' 11"24' 7"21' 5"
350S137-9716" oc28' 1"22' 4"19' 6"
350S137-9724" oc24' 7"19' 6"17' 0"

Table 5: 3-1/2" interior wall heights, 5 psf lateral load. Source: ClarkDietrich Structural Interior Wall Heights (IBC 2024 / AISI S100-16 w/S2-20).

Note: ClarkDietrich also publishes separate limiting height charts for all of their ProSTUD non-structural and structural drywall framing systems. The tables above are examples for 2-1/2″ and 3-1/2″. For other limiting heights tables for non-structural and structural framing members, visit ClarkDietrich’s iTools.

Exterior Curtain Wall Heights

Curtain wall framing is the structural steel stud backup behind exterior cladding — brick, stone, EIFS, stucco, metal panels. These walls take wind, not just occupancy pressure, and that changes everything about how you size the stud.

Instead of 5 psf lateral load, you’re dealing with wind pressures that might be 15, 20, 25 psf or higher depending on where you’re building and how tall the building is. And instead of L/240 or L/360, the deflection limit is set by the cladding material — most critically, brick requires a much tighter limit than EIFS.

First: convert your wind pressure before using the table.

This is the step that trips people up most often. Since 2012, building codes express design wind pressure as a strength-level (LRFD) value. But curtain wall limiting height tables — including ClarkDietrich’s — are built around service-level (ASD) values. You have to convert before you look anything up:

ASD wind pressure = LRFD wind pressure × 0.6

Your structural drawings (General Notes page) will show the LRFD value. Multiply by 0.6 and use that number to enter the table. Example: drawings show 25 psf → 25 × 0.6 = 15 psf ASD → use the 15 psf column.

Deflection limits depend on what’s cladding the wall.

Table 6 shows which deflection limit applies to each cladding type. The jump from L/240 (EIFS) to L/600 (brick) is significant — a brick-clad wall at the same height and wind pressure might need a stud one or two gauges heavier than an EIFS wall. That cost difference needs to be in the bid.

Exterior cladding Deflection limit Why it matters
EIFS, exterior siding, gypsum sheathingL/240Most flexible; these materials can handle more movement
Exterior stuccoL/360Stucco cracks under movement — needs a stiffer backup
Brick veneerL/600Brick is rigid and unforgiving — requires a significantly stiffer assembly
Brick veneer (more restrictive specs)L/720Some project specs or jurisdictions require even tighter

Table 6: Which deflection limit to use based on exterior cladding type. Source: ClarkDietrich Structural Exterior Curtain Wall Heights (IBC 2024 / AISI S100-16 w/S2-20).

Tables 7, 8, and 9 show curtain wall heights for 3-5/8″, 8″, and 12″ structural studs at ASD wind pressures of 15, 20, and 25 psf.

Stud Spacing 15 psf / L/240 15 psf / L/360 15 psf / L/600 20 psf / L/240 20 psf / L/360 20 psf / L/600 25 psf / L/240 25 psf / L/360 25 psf / L/600
362S200-4312" oc17' 4"15' 1"12' 9"15' 9"13' 9"11' 7"14' 8"12' 9"10' 9"
362S200-4316" oc15' 9"13' 9"11' 7"14' 4"12' 6"10' 7"13' 0"11' 7"9' 10"
362S200-4324" oc13' 8"12' 0"10' 2"11' 10"10' 11"9' 3"10' 7"10' 2"8' 7"
362S200-6812" oc19' 11"17' 5"14' 8"18' 1"15' 10"13' 4"16' 10"14' 8"12' 5"
362S200-6816" oc18' 1"15' 10"13' 4"16' 5"14' 4"12' 1"15' 3"13' 4"11' 3"
362S200-9712" oc22' 0"19' 3"16' 2"20' 0"17' 6"14' 9"18' 7"16' 3"13' 8"
362S200-9716" oc20' 0"17' 6"14' 9"18' 2"15' 11"13' 5"16' 11"14' 9"12' 5"

Table 7: 3-5/8" curtain wall heights (ASD wind). Wind pressures are service-level ASD values — if your drawings show an LRFD value, multiply by 0.6 first. Curtain wall studs use a 2" flange (S200) rather than the 1-5/8" flange common in interior work. Source: ClarkDietrich Structural Exterior Curtain Wall Heights (IBC 2024 / AISI S100-16 w/S2-20).

Stud Spacing 15 psf / L/240 15 psf / L/360 15 psf / L/600 20 psf / L/240 20 psf / L/360 20 psf / L/600 25 psf / L/240 25 psf / L/360 25 psf / L/600
800S162-5412" oc32' 8"28' 7"24' 1"29' 9"25' 11"21' 11"27' 7"24' 1"20' 4"
800S162-5416" oc29' 9"25' 11"21' 11"27' 3"23' 7"19' 11"25' 1"21' 11"18' 6"
800S162-6812" oc35' 4"30' 10"26' 0"32' 1"28' 1"23' 8"29' 10"26' 0"22' 0"
800S162-6816" oc32' 1"28' 1"23' 8"29' 2"25' 6"21' 6"27' 1"23' 8"19' 11"
800S162-9712" oc37' 9"32' 11"27' 10"34' 3"29' 11"25' 3"31' 10"27' 10"23' 6"
800S162-9716" oc34' 3"29' 11"25' 3"31' 2"27' 2"22' 11"28' 11"25' 3"21' 4"

Table 8: 8" curtain wall heights (ASD wind). Source: ClarkDietrich Structural Exterior Curtain Wall Heights (IBC 2024 / AISI S100-16 w/S2-20).

Stud Spacing 15 psf / L/240 15 psf / L/360 15 psf / L/600 25 psf / L/240 25 psf / L/360 25 psf / L/600
1200S162-6812" oc48' 7"42' 6"35' 10"41' 0"35' 10"30' 2"
1200S162-6816" oc44' 2"38' 7"32' 6"35' 8"32' 6"27' 5"
1200S162-9712" oc55' 1"48' 1"40' 7"46' 5"40' 7"34' 3"
1200S162-9716" oc50' 0"43' 8"36' 10"42' 2"36' 10"31' 1"
1200S200-9712" oc57' 4"50' 1"42' 3"48' 4"42' 3"35' 8"
1200S200-9716" oc52' 1"45' 6"38' 5"43' 11"38' 5"32' 4"

Table 9: 12" curtain wall heights (ASD wind) — used for high-rise and high-wind applications. Source: ClarkDietrich Structural Exterior Curtain Wall Heights (IBC 2024 / AISI S100-16 w/S2-20).

Floor Joist Span Tables

Floor joist tables are different from wall tables in one important way: you have to satisfy two deflection checks at the same time, not just one.

The two checks are:

  • Total load deflection — the full weight of the floor system, checked against L/240
  • Live load deflection — just the occupancy load (people, furniture, equipment), checked against L/360 or L/480 depending on the spec

Both have to pass. The one that gives you the shorter allowable span is the one that governs. The ClarkDietrich tables show both columns side by side so you can see which one controls for your configuration.

Single span vs. two equal spans

The tables also break out two scenarios. Single span is a joist running between two supports with no bearing point in the middle. Two equal spans is a joist running continuously over an interior bearing wall or beam — the table value in that case is the distance from the end support to the center support, not the total joist length. Continuous joists can span noticeably further than single-span joists of the same size, which is worth knowing at layout time.

Web stiffener notations

Floor joist tables use three stiffener notations:

  • “e” — stiffeners required at end supports only
  • “i” — stiffeners required at the interior (center) support only
  • “a” — stiffeners required at all supports

These are requirements, not suggestions. If the table value has a notation and you don’t install the stiffeners, that span value doesn’t apply to your assembly.

Tables 10 and 11 show reference spans for 6″ and 8″ joists.

Member Fy (ksi) Single span — LL: L/360 Two equal span — LL: L/360 Single span — LL: L/480 Two equal span — LL: L/480
12" oc16" oc24" oc 12" oc16" oc24" oc 12" oc16" oc24" oc 12" oc16" oc24" oc
600S137-433315' 10"13' 8"11' 2"15' 10" i13' 8" i11' 2" i14' 11"13' 7"11' 2"15' 10" i13' 8" i11' 2" i
600S137-545017' 8"16' 0"14' 0"19' 10"18' 0" i14' 11" i16' 0"14' 7"12' 9"18' 0"16' 4"14' 4" i
600S162-545018' 5"16' 9"14' 7"20' 8"18' 9" i16' 1" i16' 9"15' 2"13' 3"18' 9"17' 1"14' 11" i
600S162-685019' 9"17' 11"15' 8"22' 2"20' 2"17' 7" i17' 11"16' 4"14' 3"20' 2"18' 4"16' 0"
600S162-975021' 11"19' 11"17' 4"24' 7"22' 4"19' 6"19' 11"18' 1"15' 9"22' 4"20' 3"17' 9"
600S200-685020' 9"18' 10"16' 6"23' 4"21' 2"18' 6" i18' 10"17' 2"15' 0"21' 2"19' 3"16' 10"
600S200-975023' 1"20' 11"18' 4"25' 11"23' 6"20' 7"20' 11"19' 0"16' 8"23' 6"21' 4"18' 8"
600S300-975025' 2"22' 10"20' 0"28' 3"25' 8"22' 5"22' 10"20' 9"18' 2"25' 8"23' 4"20' 4"

Table 10: 6" floor joist allowable spans. Total load deflection limit: L/240. Live load deflection limit: L/360 or L/480 — check both columns; shorter span governs. "i" = web stiffeners required at interior support. Source: ClarkDietrich Floor Joist Span Tables (IBC 2024 / AISI S100-16 w/S2-20).

Member Fy (ksi) Single span — LL: L/360 Two equal span — LL: L/360 Single span — LL: L/480 Two equal span — LL: L/480
12" oc16" oc24" oc 12" oc16" oc24" oc 12" oc16" oc24" oc 12" oc16" oc24" oc
800S137-433318' 4"15' 10"12' 11" e18' 4" i15' 10" i12' 11" i18' 4"15' 10"12' 11" e18' 4" i15' 10" i12' 11" i
800S137-545022' 2"20' 2"17' 4"24' 6" i21' 3" i17' 4" i20' 2"18' 3"16' 0"22' 7" i20' 6" i17' 4" i
800S137-685023' 11"21' 9"19' 0"26' 11"24' 5" i20' 5" i21' 9"19' 9"17' 3"24' 5"22' 2"19' 5" i
800S162-685025' 7"23' 3"20' 4"28' 9"26' 1"22' 9" i23' 3"21' 2"18' 6"26' 1"23' 9"20' 9"
800S137-975026' 7"24' 2"21' 1"29' 10"27' 1"23' 8"24' 2"21' 11"19' 2"27' 1"24' 8"21' 6"
800S162-975028' 7"25' 11"22' 8"32' 1"29' 2"25' 5" i25' 11"23' 7"20' 7"29' 2"26' 6"23' 2"

Table 11: 8" floor joist allowable spans. Total load deflection limit: L/240. Live load: L/360 or L/480 — check both; shorter governs. "e" = web stiffeners at end support; "i" = web stiffeners at interior support. Source: ClarkDietrich Floor Joist Span Tables (IBC 2024 / AISI S100-16 w/S2-20).

Ceiling Framing Span Tables

Ceiling framing spans cover the members that support suspended ceiling assemblies — ProSTUD used as ceiling joists, hat/furring channel in direct-attach systems, and cold-rolled U-channel in grid applications. The load input is simply the dead weight of the ceiling assembly: gypsum board, finishes, insulation, and any fixtures or mechanical elements hanging from it.

ClarkDietrich publishes three ceiling span tables — one each for ProSTUD, furring channel, and U-channel. Dead load values used are 4 psf (light assembly), 6 psf (medium), and 13 psf (heavy — multiple gypsum layers, tile, or significant mechanical load).

A big difference in ProSTUD ceiling spans: bracing

ProSTUD ceiling tables split values into two conditions based on whether the compression flange is braced at mid-span or not. Adding a single bracing point at mid-span makes a meaningful difference. For example, a 600PDS125-33 at 24″ spacing and 4 psf jumps from 11’3″ (unbraced) to 16’3″ (mid-span braced) — a 44% increase in allowable span from one bracing point. See Table 12.

Member Fy (ksi) 4 psf — Unsupported 4 psf — Mid-span braced 6 psf — Unsupported 6 psf — Mid-span braced
12" oc16" oc24" oc 12" oc16" oc24" oc 12" oc16" oc24" oc 12" oc16" oc24" oc
162PDS125-15507' 3"6' 8"5' 11"7' 10"7' 2"6' 3"6' 5"5' 11"5' 3"6' 10"6' 3"5' 5"
250PDS125-15508' 4"7' 8"6' 11"10' 11"9' 11"8' 8"7' 5"6' 11"6' 2"9' 7"8' 8"7' 7"
362PDS125-15509' 2"8' 6"7' 7"12' 9"11' 8"10' 3"8' 3"7' 7"6' 9"11' 3"10' 3"8' 11" e
600PDS125-155010' 8"9' 10"8' 10"15' 0"13' 9"12' 2"9' 6"8' 10"7' 11"13' 3"12' 2"9' 11" e
362PDS125-333311' 8"10' 9"9' 8"16' 8"15' 5"13' 11"10' 5"9' 8"8' 8"15' 0"13' 11"12' 6"
600PDS125-333313' 6"12' 6"11' 3"19' 6"18' 1"16' 3"11' 9"10' 11"9' 10"17' 0"15' 8"14' 1"

Table 12: ProSTUD ceiling spans, L/240 deflection limit. A single mid-span bracing point substantially increases allowable span — a 600PDS125-33 at 24" oc, 4 psf goes from 11' 3" unbraced to 16' 3" with mid-span bracing. "e" = web stiffeners required at support. Source: ClarkDietrich ProSTUD Allowable Ceiling Spans (IBC 2024 / AISI S100 / AISI S220).

Table 13 shows furring channel ceiling spans at L/360.

Member Span type 4 psf 6 psf 13 psf
12" oc16" oc24" oc 12" oc16" oc24" oc 12" oc16" oc24" oc
087F125-18Single4' 5"4' 0"3' 6"3' 10"3' 6"3' 1"3' 0"2' 9"2' 5"
087F125-18Multiple5' 6"5' 0"4' 4"4' 9"4' 4"3' 10"3' 8"3' 4"2' 10"
087F125-33Single5' 7"5' 1"4' 5"4' 10"4' 5"3' 10"3' 9"3' 5"3' 0"
087F125-33Multiple6' 11"6' 3"5' 6"6' 0"5' 6"4' 9"4' 8"4' 3"3' 8"
150F125-33Single8' 6"7' 8"6' 9"7' 5"6' 9"5' 10"5' 9"5' 2"4' 6"
150F125-33Multiple10' 6"9' 6"8' 4"9' 2"8' 4"7' 3"7' 1"6' 5"5' 7"
150F125-43Single9' 2"8' 4"7' 4"8' 0"7' 4"6' 4"6' 2"5' 8"4' 11"
150F125-43Multiple11' 4"10' 4"9' 0"9' 11"9' 0"7' 11"7' 8"7' 0"6' 1"
150F125-54Single9' 10"8' 11"7' 9"8' 7"7' 9"6' 10"6' 8"6' 0"5' 3"
150F125-54Multiple12' 2"11' 0"9' 8"10' 7"9' 8"8' 5"8' 2"7' 5"6' 6"

Table 13: Furring (hat) channel ceiling spans, L/360 deflection limit. "Multiple" = continuous over several supports, which allows longer spans than single. Source: ClarkDietrich Furring Channel Properties and Spans (IBC 2024 / AISI S100-16 w/S2-20).

How to Read a Stud Designation

Every stud, joist, and furring member uses a designation code that tells you exactly what you’re looking at. Once you know the pattern, you can decode any member instantly. Table 14 breaks it down, and Table 15 shows the gauge-to-mil conversion you’ll need when ordering.

Segment What it means Example: 600S162-54
First number (e.g., 600)Web depth in hundredths of an inch600 = 6" web
Letter(s) — S, F, or PDSShape: S = C-stud, F = furring channel, PDS = ProSTUDS = C-stud
Middle number (e.g., 162)Flange width in hundredths of an inch162 = 1-5/8" flange
Number after dash (e.g., 54)Steel thickness in mils (thousandths of an inch)54 mil ≈ 16 gauge

Table 14: How to read a CFS member designation code.

Nominal Gauge Design Thickness (mils) Where it's typically used
25 ga18 milLightest partition / ceiling framing
20 ga33 milStandard commercial partition
18 ga43 milHeavier partition, light structural
16 ga54 milStructural — walls, joists, curtain wall
14 ga68 milHeavy structural — tall walls, curtain wall, floor joists
12 ga97 milVery heavy structural — high-rise curtain wall, long-span joists

Table 15: Gauge-to-mil reference. Always specify by mils when ordering — nominal gauge labels can vary by manufacturer.

The thickness (mil) number is the most important one to get right when ordering. Nominal gauge numbers can vary by manufacturer; mil thickness does not. Always spec and order by mils.

Mistakes to Avoid

Using the wrong table for the assembly. An interior wall table and a curtain wall table might both list an 800S162-68, but the numbers mean completely different things. The interior table sizes against 5 psf occupancy pressure; the curtain wall table sizes against 15–40 psf wind. The floor joist table works off gravity loads entirely. Pull the wrong table and the number you read out doesn’t apply to your wall.

Skipping the wind pressure conversion on curtain walls. Project structural drawings show LRFD wind pressures. Manufacturer curtain wall tables use ASD values. Multiply the drawing value by 0.6 before entering the table — if you go straight to the table with the LRFD number, you’ll land in the wrong column.

Checking only one deflection limit on floor joists. Both the total load check and the live load check have to pass. Check both and use the shorter span.

Using the wrong deflection limit for the finish or cladding. L/240 is right for standard gypsum. It’s not right for tile, plaster, stucco, or brick. Tile needs L/360. Brick typically needs L/600. Using the looser limit means the stud will flex more than the finish can handle — and you’ll find out about it after the job is done.

Ignoring the “e,” “i,” and “a” notations. When a table value has one of these letters next to it, web stiffeners are required at that bearing location. Without them, the published value doesn’t hold.

Assuming limiting height means the stud can carry a vertical load. Every table covered here is a deflection check under lateral or gravity load — not a vertical load capacity check. If a wall is load-bearing, these tables don’t cover it. That’s a separate calculation requiring an engineer.

Need Studs or Track for Your Next Job?

The Formetal Company has been supplying cold-formed steel studs and track in Forest Park, Georgia since 1959. We supply structural and non-structural framing to contractors across Atlanta, the Southeast, and nationwide — with custom lengths available for tall walls and long-span applications where standard stock won’t reach.

  • Get project pricing: Use our Quote Builder for fast stud and track pricing.
  • Product data and submittals: Visit our Submittal Builder page for section properties and compliance documentation, and to build your own submittal package. Visit our Products page for a full list of all products we carry. 
  • Talk to our team: Contact us for custom lengths, sizing questions, or bulk pricing.

 

All limiting height and span data in this article is sourced from ClarkDietrich’s published load table documents — Structural Interior Wall Heights, Structural Exterior Curtain Wall Heights, Floor Joist Span Tables, ProSTUD Allowable Ceiling Spans, and Furring Channel Properties & Spans — all complying with AISI S100-16 (2020) w/S2-20 and IBC 2024. Wind pressures in exterior curtain wall tables are ASD service-level values; multiply LRFD values by 0.6 before use. Web stiffener notations (“e,” “i,” “a”) are required conditions. Always verify values against current manufacturer documentation and applicable local codes. For load-bearing, engineered, or code-critical work, consult a licensed structural engineer.